WHAT'S NEW


WD100 / WD150 / WD175 / WD185 / WD300 / WD300LV / WDE300 / W0168 / W0241/ WE0168 / WAI7
Generally, pressure and temperature Swichgage® contacts are wired to a central nerve center called a Magnetic Switch or Tattletale® annunciator. This nerve center is essentially a relay and, when signaled by a Swichgage contact operation, it either makes or breaks a circuit to operate an alarm or engine shutdown device. Various nerve centers are used depending on the operation to be performed, the type of electrical power available and the type of alarm or shutdown device used.
Typical wiring diagrams for the popular Tattletale annunciators and magnetic switches are linked to this page as pdf files for downloading. If a drawing of the specific model number is available, please refer to that drawing for specific wiring instructions.
The following Installation Instructions are typical for a variety of W-Series Engine Panels and may not reflect the exact configuration for your panel assembly. It is assumed that the installer is familiar with engine operations and has basic mechanical and electrical skills. If additional assistance is needed, please call Jay Ottaviano at MurCal. Jay is our inside technical sales rep. It is also recommended that you conduct a visual inspection for damage which may have occured during shipment. Download the 7-page instruction booklet by clicking here or by clicking on the image in the next paragraph.
W-Series Engine Panels Installation InstructionsTo download this 7-page Installation Instruction booklet you may either click on the image to the right or simply click here.
Now that you've downloaded the general installation instructions for the W-Series Panels we'll move on to more specific information regarding the wiring of your panel. Below you will find bulletins and wiring diagrams for each panel type. Just scroll down the page looking for the panel you own. Once again, each information bulletin and wiring diagram will be available for you to download as a pdf file.
WD100 / WD150 / WD175 / WD185Click Here to download the WD100 Sales Bulletin (pdf file)
Click Here to download the WD100 Wiring Diagram (pdf file)
518PH Tattletale® Magnetic Switch with Mechanical Swichgages®
This is a basic "Energize To Run Panel". It will keep power on from the "NC" terminal to your run circuit unless you have a safety condition on oil pressure or coolant temperature. Typically this panel will control the ignition coil, an inline fuel valve or a push/pull solenoid for shutdown. NOTE: This is an immediate shutdown device.
WD300 / WD300LVClick Here to download the WD300 Sales Bulletin (pdf file)
Click Here to download the WD300 Wiring Diagram (pdf file)
117PH Tattletale® Magnetic Switch with Mechanical Swichgages® / Emergency Stop Push Button
This is a basic "Energize To Run Panel". It will keep power on from the "NC" terminal to your run circuit unless you have a safety condition on oil pressure or coolant temperature. Typically this panel will control the ignition coil, an inline fuel valve or a push/pull solenoid for shutdown. NOTE: This is an immediate shutdown device, typically used on stand-alone engines.
WDE300
W0168
WE0168
W0241
WAI7Click Here to download the WAI7 Sales Bulletin (pdf file)
Click Here to download the WAI7 Installation Instructions (pdf file)
Click Here to download the WAI7 Wiring Diagram (pdf file)
760AF Tattletale® Magnetic Switch with Mechanical Swichgages®
This is a standard Murphy panel that is perfectly suited for on and off road mobile applications. The WAI Panel Series can be wired for delay on both start and stop. These panels feature a flashing light and a mini-siren which sounds an alarm for 30 seconds before shutdown, giving the operator an opportunity to pull over. The mechanical Swichgage® instruments are internally illuminated for viewing at night and the panels are easy to mount under-dash with a 270° pivoting bracket.